Transformer Loss Tester, Load & No Load Tester, No Load Characteristics Tester manufacturer / supplier in China, offering Transformer Load & No-Load Loss Tester, DC system Matainence Comprehensive Battery Test Set, Portable multi-function digital three phase cable power quality analyzer and so on.

Gold Member Since 2017
Audited Supplier

Transformer Load & No-Load Loss Tester

Get Latest Price
Min. Order / Reference FOB Price
1 Piece US $2,000-2,500/ Piece
Port: Wuhan, China
Production Capacity: 2000 PCS/Month
Payment Terms: L/C, T/T, Western Union, Paypal, Money Gram
Display: LCD
Power Supply: 160V ~ 260V
Voltage measuring: 0-750V
Current measuring: 0-100A
Working environment: -10 ºC ~ +40 ºC
Transport Package: Carton

You Might Also Like


Basic Info

Model NO.: ZX-BZL
Trademark: GDZX
Origin: China
HS Code: 9030820000

Product Description

Transformer Load & No-Load Loss Tester


 Accurately measure the distribution transformer capacity
 Measure transformer no load current, no load loss, short-circuit voltage, short circuit (load) loss.
 Auto correct wave form, temperature, non-rated voltage, non-rated current
 Allow connection with external CT PT for extending measuring range
 Max measuring voltage 750V
 800*480 LCD touch screen, friendly interface, brightness adjustable, adapts to all seasons.
 Built-in panel-type thermal printer, fast print test results.


1 Input
1) active part
    voltage measurement range: 0 ~ 10V
    current measurement range: 0 ~ 10A

2) passive part
    voltage measurement range: 0 ~ 750V ( can connect to external PT)
    current measurement range: 0 ~ 100A auto ranging (can connect to CT)

2. Accuracy
1) Voltage / Current / Frequency: ± 0.2%
2) Power: ± 0.5% (CosΦ> 0.1), ± 1.0% (0.02 <CosΦ<0.1)

3. Operating temperature: -10 ºC ~ +40 ºC

4. Charging power supply: AC 160V ~ 260V

5. Insulation
1) The insulation resistance of the voltage and current input terminals to the chassis ≥100MΩ
2) working power input to the shell can withstand power frequency 2kV (rms) 1 minute test

6. Volume: 32 × 24 × 13cm, Net Weight: 3Kg