Introduction
Transformer winding deformation tester consists of measuring part and analysis software part. The measurement part is under high-speed microcontroller control, capable of signal generation and signal measurement. The measurement section is connected to the tablet via the wireless WIFI interface. It is not wired, easy to use, and can be connected to a tablet or laptop using wireless Bluetooth and USB.
Features
1. In the test process only need to remove the transformer connection bus.
3. Sweeping frequency up to 10MHz, scanning interval can be 0.25kHz, 0.5kHz, 1kHz for multiple analysis
4. High intelligent, auto range adjustment, auto sampling frequency adjustment.
5. Windows platform, compatible with Win98 / 2000 / XP / Win7 system.
6. Historical curve comparison analysis, max 6 curves observation, auto analysis and diagnosis system
7. Auto save environment parameters and testing results, color printing function
8. Humanized software design, more convenient to use.
9. Auto complete the test after wiring, duringmeasurement check historical curves or stop at any time
10. Measurement time less than 60 seconds for every phase, 10 minutes for whole transformer windings testing.
Parameters
Two scaning methods |
Linear scaning range |
(10Hz) - (10MHz) 40000 dots |
Resolution |
0.25kHz, 0.5kHz, 1kHz |
Section scaning range |
(0.5kHz) - (1MHz), 2000 dots |
(0.5kHz)-(10kHz), (10kHz)-(100kHz), (100kHz)-(500kHz), (500kHz)-(1000kHz) |
Test range |
-120dB to +20dB |
Test accuracy |
0.1dB |
Scaning frequency accuracy |
0.01% |
Signal input impedance |
1MΩ |
Signal output impedance |
50Ω |
Signal output range |
±20V |
Repetition rate of same phase measurement |
99.9% |
Equipment Size |
300×340×120(mm) |
Carrying box Size |
310×400×330(mm) |
Total weight |
10Kg |