Internal Water Cooling Generator Insulation tester Alternator Impedance tester

Product Details
Customization: Available
After-sales Service: Provided
Warranty: 1 Year
Manufacturer/Factory & Trading Company
Gold Member Since 2017

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Number of Employees
40
Year of Establishment
2012-02-28
  • Internal Water Cooling Generator Insulation tester Alternator Impedance tester
  • Internal Water Cooling Generator Insulation tester Alternator Impedance tester
  • Internal Water Cooling Generator Insulation tester Alternator Impedance tester
  • Internal Water Cooling Generator Insulation tester Alternator Impedance tester
  • Internal Water Cooling Generator Insulation tester Alternator Impedance tester
  • Internal Water Cooling Generator Insulation tester Alternator Impedance tester
Find Similar Products

Basic Info.

Model NO.
ZXC38
Display
digital display plus simulation progress bar displ
Test range
0.1 MOhm-200GOhm
Accuracy
+/-(10%+ 5words)
Temperature measurement
-25-125centigrade
Test Voltage
2.5kV, 5.0kV FOR OPTIONS
Output short circuit current
Greater than or equal to 25mA
Measuring time
1 min-10 min ( related to testing method)
Charging Power supply
180-270VAC, 50Hz/60Hz+/-1%
Working temperature and humidity
-10-40centigrade, 20-80%RH
Transport Package
Carton
Specification
With the change of technical scheme
Trademark
GDZX
Origin
China
HS Code
9030332000
Production Capacity
500PCS/Month

Product Description

Internal Water Cooling Generator Insulation tester Alternator Impedance tester

Introduction
Internal Water Cooling Generator Insulation tester Alternator Impedance tester

      ZXC38 Internal Water cooling generator Insulation Tester can be used for measuring internal water cooling generator or laboratory insulation test.

 


Technical Indicators

1. Test range: 0.1 MΩ-200GΩ
2. Accuracy: ± (10%+ 5words)
3. Display: digital display plus simulation progress bar display
4. Temperature measurement: -25ºC~125ºC
5. Test Voltage: 2.5kV, 5.0kV FOR OPTIONS
6. Output short circuit current: ≥25mA
7. Measuring time: s 1 min ~ 10 min ( related to testing method)
8. Charging Power supply: 180~270VAC, 50Hz/60Hz±1%
9. Working temperature and humidity: -10 ºC~ 40 ºC, 20~80%RH

Internal Water Cooling Generator Insulation tester Alternator Impedance tester

Device display
Internal Water Cooling Generator Insulation tester Alternator Impedance tester
About GDZX
Wuhan GDZX Power Equipment Co.,Ltd.is a manufacturer of power test equipment, integrating design, production and sales, providing complete solutions for high-voltage testing and electrical testing services for various power users.The main products include:AC series resonance test device, high voltage test equipment, transformer test equipment, secondary protection / switch test equipment, cable fault tester, arrester test equipment, power metering equipment, standard source series and so on. There are many kinds of products and complete models.
Internal Water Cooling Generator Insulation tester Alternator Impedance tester
Internal Water Cooling Generator Insulation tester Alternator Impedance tester
Internal Water Cooling Generator Insulation tester Alternator Impedance testerInternal Water Cooling Generator Insulation tester Alternator Impedance testerInternal Water Cooling Generator Insulation tester Alternator Impedance tester
Internal Water Cooling Generator Insulation tester Alternator Impedance tester
Shipping and packaging
Internal Water Cooling Generator Insulation tester Alternator Impedance tester

Features

1. 32 bit micro controller, menu operation

2. Large output current (>25mA under 2500V), short circuit current>=25mA

3. safe and reliable with hv generator fully enclosed and with protective resistor inside.

4. strong anti-interference ability, can satisfy EHV substation site operation

5. auto discharge after test and real-time monitor discharge process

6. suitable for measuring insulation resistance, DAR ( R60S/R15S) and PI (R10min/R1min) of water cooled generator

7. testing voltage 2500V/5000V, can measure up to 2TΩ insulation resistance

8. auto compensation to water polarization potential, measuring being accurate even when the resistance between the base and water collecting pipe is less than 10KΩ

9. high output power, load resistance between circuit to water collecting pipe can be as low as 100kΩ (2500V)/150kΩ(5000V),insulation resistance can be low as 1MΩ(2500V)/2MΩ(5000V)

10. simulation progress bar displaying the insulation resistance value, logarithmic scale, easy to read

11. Three and a half bit LCD digital meter

12. Time display (minute/second, 32 minutes a cycle), and beep every 15 seconds,

13. auto test and record value of R15S, R60S, R10min, DAP, PI

     