ZXPD-200L Series Partial Discharge Detector can be widely used in theater detection of power system, including insulation state detection of high-voltage switch cabinet, ring network cabinet, voltage / current transformer, transformer (including dry-type transformer), GIS, overhead line, cable and other equipment.
1. Simultaneous interpreting PDsignals of almost all electrical equipment with different sensors.
2. Provide time-domain waveform, PRPD, PRPS and other discharge patterns to realize the analysis of different discharge types.
3. The human-computer interface facilitates the data management of different equipment, including the tracing of historical data change trend, horizontal and vertical data analysis, so as to realize 360° comprehensive diagnosis of the tested equipment.
4. Built in ultrasonic sensor and transient ground voltage (hereinafter referred to as TEV) sensor, which can be externally connected with transformer, GIS, overhead line, cable and other special sensors.
5. It is more convenient to use the non-invasive detection method than the traditional pulse PD detector because there is no need to cut off the power supply or apply high voltage source during the test.
6. The test bandwidth range is 30kHz ~ 2.0GHz, which is applicable to the detection principle of various frequency bands.
Technical Indicators
TEV measurement | UHF measurement | ||
Measuring range | 0-60 dBmV | Detection frequency band | 300-1500MHz |
Resolution | 1dB | Measuring range | -75dBm-0dBm |
Accuracy | ±1dB | Accuracy | <1dBmV |
Maximum pulse per cycle | 1400 | Sensor band | 300-2000MHz |
Measurement frequency band | 1~100MHz | ||
AA measurement | AE measurement | ||
Measuring range | -6dBμV to 68dBμV | Measuring range | -6dBμV to 68dBμV |
Resolution | 1dB | Resolution | 1dB |
Accuracy | ±1dB | Accuracy | ±1dB |
Sensor center frequency | 40 kHz | Frequency range | 40~200 kHz |
HFCT measurement | |||
Transducer transmission impedance | 5mV/mA | ||
Detection frequency | 1~30MHz | ||
Sensitivity | ≤50pC | ||
Hardware | |||
Shell | ABS | ||
Display | 5.0-inch RGB LCD | ||
Controller | ARM | ||
Connector | USB interface (with charger input) 3.5mm stereoheadphone jack External ultrasonic sensor input |
Wireless WiFi Wireless synchronization reference |
|
Headset | 8 ohms | ||
SD card | Standard 16G | ||
Built in battery | 3.7V/1Ah lithium battery | ||
Working hours | About 8 hours | ||
Charger | AC 90-264V or DC 5V | ||
Temperature | -20 ~ 50ºC | ||
Humidity | 20-85% RH | ||
Weight | 0.4KG (Host) |
Product pictures