Customization: | Available |
---|---|
After-sales Service: | Provided |
Warranty: | 1 Year |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Comprehensive Tester For Volt Ampere Characteristics Of Transformer
Introduction
Usage | CT,PT | |
Output | 0~180Vrms,12Arms,36A(peak value) | |
Voltage measurement accuracy | ±0.2% | |
CT Ratio | Range | 1~40000 |
Accuracy | ±0.1% | |
PT Ratio | Range | 1~40000 |
Accuracy | ±0.1% | |
Phase | Range | ±2min |
Accuracy | 0.5min | |
DC resistance | Range | 0~300Ω |
Accuracy | 0.2%±2mΩ | |
Burden | Range | 0~1000VA |
Accuracy | 0.2%±0.02VA | |
Power supply | AC220V±10%,50Hz | |
Environmental Conditions | Operating temperature:-10ºC~50ºC Humidity :≤90% |
|
Weight and Dimensions | Dimensions: 365 mm×290 mm×153mm, Weight<10kg |
Company introduction
Wuhan GDZX Power Equipment Co.,Ltd.is a manufacturer of power test equipment, integrating design, production and sales, providing complete solutions for high-voltage testing and electrical testing services for various power users.The main products include:AC series resonance test device, high voltage test equipment, transformer test equipment, secondary protection / switch test equipment, cable fault tester, arrester test equipment, power metering equipment, standard source series and so on. There are many kinds of products and complete models.
Service and Warranty
Service
* Provide professional consulting service; dedicated salesman and professional technical engineer to answer customer questions.
* Ensure customer get the detailed information about the product in hand.
* Reasonable price, we trust our customers should get the worth what they paid. Quotation stamped and confirmed by Manager.
* Welcome customers visit.
PACKING AND SHIPPING
(1)We will ship products within 8-20 working days after the receipt of confirmation of your payment.
Features
1. Full-featured, not only satisfy the test requirements of various CTs (include TP class), such as the excitation characteristics (i.e., volt-ampere characteristics), ratio, polarity, secondary winding resistance, secondary burden, ratio error and phase displacement, but can also be used for the tests of various PTs, including excitation characteristics of the electromagnetic unit, ratio, polarity, secondary winding resistance, ratio error and phase displacement.
2. Automatically give CT, VT parameters, including knee point voltage / current, 10% error curve, the accuracy limit factor (ALF), instrument security factor (FS), the second time constant (Ts), remanence coefficient (Kr), saturated and unsaturated inductance etc.
3. Test meet IEC60044 GB1208 (-1) GB16847 (IEC60044-6) became etc all kinds of transformer standards, and in accordance with the transformer types and levels of automatic choose which standard test
4. Based on advanced principle of low-frequency test method that can meet the CT test on knee voltage up to 60KV.
5. Friendly interface beautiful, all English graphic interface
6. The instrument can store 1000 groups of test data that won't be lost when power off. After test ended, the data can be coped to PC by USB disk for analysis and being transformed into WORD report.
7. Test is simple and convenient; one-click can complete tests of CT secondary resistance, excitation, ratio and polarity.
Easy to carry, because the weight is less than 10Kg.