After-sales Service: | Provide |
---|---|
Warranty: | 1 Year |
Rated voltage: | 0V~400V; 20% overflow are not allowed |
AC voltage RMS accuracy: | +/-0.1% |
AC current RMS accuracy: | +/-0.1%(plit transformer:+/-0.2%) |
Active power: | +/-0.1%(split transformer: +/-0.2%) |
Customization: |
---|
Suppliers with verified business licenses
Technical Indicators
1.Power energy measurement: | ±0.1%(built-in transformer)±0.2%(split transformer |
2.Rated voltage: | 0V~400V, 20% overflow are not allowed |
3..Rated current: | built-in transformer 0~10A, Split type transformer: 20A or 100A,500A,1000A,2000A(optional)20% overflow are not allowed |
4.AC voltage RMS accuracy: | ±0.1% |
5.AC current RMS accuracy: | ±0.1%(split transformer:±0.2%) |
6.Active power: | ±0.1%(split transformer:±0.2%) |
7.Reactive power: | ±0.3%(split transformer:±1.0%) |
8.Frequency measurement: | 45Hz-65Hz (±0.01Hz) |
9.Angle measurement: | 0°-360°(±0.1°) |
10.Constant of impulse: | 1)0low frequency FL=6400P/kw·h 2)High frequency FH=6400×8P/kw·h |
11.Power supply: | DC 8.4V ±10% |
12.Power consumption: | 8VA |
13.Dielectric strength: | 1) the insulating resistance of voltage, current input terminal to case≥100MOhm 2) the input terminal of the working power can stand 1.5kV (RMS) to case, time is 1 minute |
14.Work temperature: | -15ºC~60ºC |
15.Relative humidity: | 0%~90% |
16.Warm-up time: | 1 minute |
17.Weight and size | 2.0KG; 32*24*13cm |
Product pictures
1. Measure a variety of electrical parameters, such as three phase voltage, current, active power, reactive power, power factor, angle, frequency, etc.
2. Can calibrate various of energy meters and other metering equipments
3. Can measure integrated error on site
4. Two current input modes for option: terminal or clamp meter
5. Show Hexagon vector diagram
6. High precision of CT turns ratio measurement
7. Can save 500 groups of data and connect to PC
8. LCD display with user-friendly interface
9. Portable
Suppliers with verified business licenses